A. Single phase inverter: 1 master+2 slaves (T58)
To balance the battery, you need to do the steps for Master battery with Slave A and Master battery with Slave B separately, as below steps:
1.Connect only master battery, discharge master battery to 10%.
2.Connect the slave A battery with the master battery, charge to 100%.
3.Disconnect the Slave A battery.
4.Discharge the master battery to 10%.
5.Connect the slave B battery with the master battery, charge to 100%.
6.Disconnect the Slave B battery.
7.Connect only the master battery and charge to 100%.
8.Then connect all the batteries.
A. Single phase inverter: 1 master+1 slaves (T58)
To balance the battery, you need to do the steps below:
1.Connect only master battery, discharge master battery to 10%.
2.Connect the slave battery with the master battery, charge to 100%.
3.Disconnect the Slave battery.
4.Connect only the master battery and charge to 100%.
5.Then connect all the batteries.
Comments
0 comments
Please sign in to leave a comment.