The inverter has an EPS function. When the grid is connected, the inverter outputs go through the Grid port, and when the grid is disconnected, the inverter outputs go through the EPS port. Ensure that the EPS load rated power is within the EPS rated output power range, otherwise, the inverter will report an "Overload" warning. When “overload” occurs, adjust the load power to make sure it is within the EPS rated output power range, and the inverter will automatically return to normal.