After connecting a laptop to the WiFi hotspot of DataHub, please login to the configuration page via http://192.168.10.10 on browser. For more details please refer to the DataHub user manual.
① On the Display D1, D2, D3, D4 of DI port, green dot means corresponding K1-K4 of RCR is closed. ② On the Enable session, enable the DI option to activate the power control settings;③ On the combobox of Setting, select the following power control functions:
A. Inverter output active power control
B. Inverter input active power control
C. Inverter output reactive power control
D. Remote shutdown ④ When Inverter output active power control is selected, input the active power value you need to set in percentage([0-100]%), and for Inverter output reactive power control, please input the Power Factor([80-100]%) and reactive power mode respectively. The reactive power mode includes OverExcited and UnderExcited;⑤ Submit and save the settings.
Note:
● Make sure to follow STEP1-5 strictly. In total there are 16 different combinations available for settings.
● Green dot means that the selected DI port 1-4 will be pulled-up to high level(12V), which matches the scenario that the co-responding K1-K4 on RCR are switched closed after receiving ripple control signal from the local grid operator.
● When the actual input pins of D1-D4 are not configured in the power control interface, the DataHub will control the connected inverters to run full power at normal condition.
● When switching from one DI combination to another one, the selection of the new DI combination will be executed. The old settings will be stopped.