Introduction
This article will introduce the Super-Backup Function on Solax Hybrid G4 inverters. With the Super-Backup function, during black-out the inverter can supply the backup loads even if there are no batteries installed.
Different from the normal backup solution with batteries, the Super-Backup solution, during EPS Mode, hybrid inverters export power only from PV panels (without batteries). As the PV input power is not stable, there will be some limitation. In order to avoid the overload①, the EPS ports (back-up loads) must be followed:
1. For single-phase inverters, the output power of EPS ports is restricted to half (50%) of the nominal output power of EPS ports (with battery). For more details in the Table1 below.
Table1. EPS output of X1-Hybrid G4 (without battery)
EPS output (without battery) |
X1-Hybrid-3.0 |
X1-Hybrid-3.7 |
X1-Hybrid-4.6 |
X1-Hybrid-5.0 |
X1-Hybrid-6.0 |
X1-Hybrid-7.5 |
Nominal output power [W] |
1500 |
1840 |
2300 |
2500 |
3000 |
3750 |
Peak apparent power [VA] (130% overload) |
1950,10s |
2400,10s |
3000,10s |
3250,10s |
3900,10s |
4900,10s |
2. For three-phase inverters, the output power of EPS ports is restricted to half (50%) of the nominal output power of EPS ports (with battery) total phase, but there are some differences about per-phase power. For more details in the Table2 below.
Table2. EPS output of X3-Hybrid G4 (without battery)
EPS output (without battery) |
X3-Hybrid-5.0 |
X3-Hybrid-6.0 |
X3-Hybrid-8.0 |
X3-Hybrid-10.0 |
X3-Hybrid-12.0 |
X3-Hybrid-15.0 |
Nominal output power [W] |
2500 |
3000 |
4000 |
5000 |
6000 |
7500 |
Per-phase power [W] |
2500 |
3000 |
4000 |
5000 |
5000 |
5000 |
Peak apparent power [VA] (130% overload) |
3250,10s |
3900,10s |
5200,10s |
6500,10s |
7800,10s |
9570,10s |
Notes:
① If PV input power is sufficient, there will not be any trouble. But if PV input power is not enough, an “EPS Overload” will be reported on the LCD.
Advantages
Some customers install the hybrid inverter first as a string inverter (Battery Ready) and add the batteries later, now they can use the back-up without battery.
Configuration
Setting path
Main → Settings → Advance Setting → EPS Setting → Super-Backup
This function is Disable by default.
If users want to supply EPS loads only with PV, just Enable it.
Compatibility
Hardware version
X1-Hybrid G4 X3-Hybrid G4
Software version
Requirement for X1-Hybrid G4:
ARM≥1.33 DSP≥1.34
Requirement for X3-Hybrid G4:
ARM≥1.30 DSP≥1.31