If the physical meter/CT is reverse-connected but Meter Direction is left at default Positive, the inverter will misinterpret import/export data, leading to incorrect Export Control behavior and potentially causing shutdowns (Meter Fault - ME:0092) or erroneous zero-export operation. Set to Negative if meter/CT is reverse-connected.