If the physical meter/CT is reverse-connected but Meter Direction
is left at default Positive
, the inverter will misinterpret import/export data, leading to incorrect Export Control
behavior and potentially causing shutdowns (Meter Fault
- ME:0092) or erroneous zero-export operation. Set to Negative
if meter/CT is reverse-connected.
Comments
0 comments
Please sign in to leave a comment.