During the heating period:
- If the cell temperature is between -30℃ and 0℃, the battery will be heated until it reaches 10℃ (heating stops then). If the cell temperature drops below 0℃ again, heating restarts.
- The system prioritizes using PV energy for heating. If PV power is insufficient:
- It draws energy from the battery if the actual SOC (State of Charge) is above 35%.
It draws energy from the grid if the actual SOC is below 35%.
For more detailes, please refer to this link: https://kb.solaxpower.com/solution/detail/2c9fa4148adb360e018b2285a506031a