The RC Fault (Residual Current Over Current Protection Fault) indicates excessive current leakage or a sudden increase of 30mA or more in the residual current. It is a general alarm related to the inverter’s safety protection mechanism.
Possible Causes
- Residual Current Over-Current: The on-grid residual current exceeds the threshold set by the safety code.
- RC Detection Device Abnormality: There may be an offset anomaly in the RC detection device.
How to Solve It
- Check Error Frequency and PE Wire:
- If the error occurs occasionally, inspect the PE (Protective Earth) wire to ensure it is properly connected and not damaged.
- Reboot the Inverter:
- Shut off the DC breaker and the AC breaker.
- Unplug and replug the PV and DC terminals.
- Turn on the breakers again.
- Firmware Upgrade:
- Perform a firmware upgrade on the inverter.
- Contact SolaX Technical Support:
- If the problem persists, contact SolaX After-sales support with the following information:
- Serial Number (SN)
- Inverter status
- Grid status
- Time period of the day when the alarm happens
- PV and AC voltage and current values
- If the problem persists, contact SolaX After-sales support with the following information: