Please follow the troubleshooting steps below:
Steps1: Confirm the DC Switch is turn on
Step2: Measuring the voltage on the PV side with a multimeter, ensure the red probe is connected to the positive terminal and the black probe to the negative terminal. The correct measurement should be a positive number within the MPPT range. If a negative number appears, it indicates that the PV wires are reversed. If the voltage is too low, wait for sufficient solar energy to start the device.
Steps3: Make sure the setting of "System ON/OFF" is on
Steps4: Make sure the setting of "Power limit" is not "0"
Steps5: Try set the safety code: user define
Step6: Measure the phase voltage of each of the three phases of L1 and N, L2 and N, and L3 and the normal value should be above 200V.
Step7: Measure the line voltage between L1 and L2, L2 and L3, and each of L1 and L3. The normal value should be around 400V.
Step8: Take the X3-hybrid G4 as an example. Check the COM connector to ensure that PIN3&6 is not short-circuited. Then check the Shutdown connector to ensure that PIN4&6 is not short-circuited.
Stesp9: Disconnect the AC and connect only PV to see if the LCD is on
Steps10: Try black start if your inverter is connected with battery, please disconnect both PV and AC, start the inverter using only battery, to see if inverter can work normally
If you have completed the above Guidance, and the problem is still not solved, please collect the following troubleshooting information contact SolaX support:
1.Basic information.(inverter SN for wifi dongle RN)
2.The PV terminal voltage.(picture)
3.Phase voltage measurement result, L1&N, L2&N, L3&N.(picture)
4.Line voltage measurement result, L1&L2, L2&L3, L1&L3.(picture)
5. Disconnect the AC and connect only PV to see if the LCD is on(picture)
6. Black start(picture)